检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
出 处:《Journal of Donghua University(English Edition)》2001年第1期46-50,共5页东华大学学报(英文版)
摘 要:A part load operation by turning the burner on and off intermittently is effective for a small scale direct fired absorption chiller. The dynamic performance of the system has been investigated. The relationship between pressure, temperature and concentration of the lithium bromide solution have been analyzed. The result obtained indicates that the pressure of the high pressure generator and the temperature of the exhausted smoke are the most sensitive parameters. It is also found that the transition time from a full load to a part load condition is quite long, and part load relative cooling capacity is almost near the intermittent running time ratio and oil consumption ratio.A part load operation by turning the burner on and off intermittently is effective for a small scale direct fired absorption chiller. The dynamic performance of the system has been investigated. The relationship between pressure, temperature and concentration of the lithium bromide solution have been analyzed. The result obtained indicates that the pressure of the high pressure generator and the temperature of the exhausted smoke are the most sensitive parameters. It is also found that the transition time from a full load to a part load condition is quite long, and part load relative cooling capacity is almost near the intermittent running time ratio and oil consumption ratio.
关 键 词:DIRECT fired ABSORPTION chiller part load DYNAMIC performance.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.38