一起SDH设备光路对接故障的分析与处理  被引量:1

Analysis and Treatment of an SDH Equipment Optical Interconnection Failure

在线阅读下载全文

作  者:王慕维[1] 杨宇方[1] 

机构地区:[1]河南省电力公司信息通信公司,河南郑州450052

出  处:《华中电力》2012年第3期20-21,26,共4页Central China Electric Power

摘  要:介绍了500kV官渡变投运时出现的一起长距离SDH光路对接故障。光路两端是不同厂家的设备,对接时一端收光正常而另一端有帧丢失告警。经分析,确认该故障由两端光口工作波长不一致导致。取消故障端预放大器后,对接成功。这起故障的分析处理,为以后不同厂家的组合式光口对接积累了经验。A long-distance optical interconnection failure caused by both ends of disaccord wavelength during 500kV Guandu substation commissioning is introduced.The optical module of each side is made by different company.One side shows a warning signal of 'lost of frame' while the other side receives light successfully.The reason of the failure is analyzed and found that different working wavelength of pre-amplifier at each side leads to the failure.After the pre-amplifier of the failure side is removed,the interconnection is succeeded.The analysis and treatment of the failure has committed experience for subsequent interconnections of combined optical modules made by different companies.

关 键 词:光口对接 波长 光功率 预放大器 

分 类 号:TN913.7[电子电信—通信与信息系统]

 