检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]中低温热能高效利用教育部重点实验室天津大学机械工程学院,天津300072
出 处:《工业建筑》2013年第S1期19-22,共4页Industrial Construction
基 金:"十一五"国家科技支撑计划重大项目(2006BAJ03A06)
摘 要:通过理论计算的方法,应用流量偏移系数法对比分析了各种典型集中供热系统的稳定性。得出如下结论:在所有的典型集中供热系统中,无源分布式变频集中供热系统稳定性最好,传统集中供热系统的稳定性次之,有源分布式变频集中供热系统的稳定性最差。有源分布式变频集中供热系统零压差点处于管网两端稳定性较好,处于管网中间稳定性较差。Using the flow offset coefficient methods the kinds typical central heating system’s stability was studied through theoretical calculations.The following conclusion was drawn: In all the typical central heating systems,the stability of the central heating system with distributed variable speed pump which does not have source pump is the best,the traditional central heating system is better,the central heating system with distributed variable speed pump which has source pump is the last;The zero pressure drop point at the two sides of the central heating system with distributed variable speed pump which has source pump is better and at the middle is worse.
分 类 号:TU995[建筑科学—供热、供燃气、通风及空调工程]