500kV变电站工频电磁场分布测量  被引量:41

Measurement of Power Frequency Electric & Magnetic Field in 500 kV Substation

在线阅读下载全文

作  者:饶章权[1] 郭启贵 赵殿全 尹玉芳 余军[1] 王建国[1] 周文俊[1] 

机构地区:[1]武汉大学电气工程学院,武汉430072 [2]长春超高压输变电局,长春130033

出  处:《高电压技术》2004年第9期41-43,共3页High Voltage Engineering

摘  要:测量了东北某变电站中 2 2 0、5 0 0kV设备区工频电磁场分布规律和变化趋势 ,结果表明站内电场和大部分磁场强度均低于ICNIRP限值 ,有些地方 (主要是电抗器 )周围磁场较大 ,虽短距离内迅速衰减 。Power frequency electric & magnetic field (PEMF) measurement in a 500 kV air insulated substation has been conducted. The distribution of power frequency electric & magnetic field along certain routes and the magnitudes beside equipment are reported. The measurement results are compared with the guidelines in standards. The results show that the values of PEMF accord with the guidelines of ICNIRP, but the values of electric field in 500 kV equipment area and magnetic field around reactor exceed the guidelines of national standard, which should be paid attention in electric power industry.

关 键 词:500KV变电站 电抗器 测量 磁场强度 场分布 电场 衰减 ICNIRP 短距离 限值 

分 类 号:TM835.4[电气工程—高电压与绝缘技术]

 