摘  要:蒸发冷却空调是以水作为制冷剂,通过在西北地区的实际工程应用,发现存在着蒸发冷却器表面结水垢以及细菌滋生等水质问题。本文针对这两大问题,从产生的原因、条件以及环境等方面进行了分析;阐述了导致上述两大问题的关键原因,提出从补水、流失水比例、水系统的软化以及抗菌剂的填加等几个环节加强水质管理的措施;通过全面的分析和研究,认为蒸发冷却器不会产生军团病。The evaporative cooling air conditioner is regard water as the refrigerant.Many water quality problemswas finded in the practical engineering application in the northwest of China.For example,it will produce sediment onthe evaporative cooler surface and breed bacterium.The paper analyses the reasons,condition and environment ofcausing these two problems.It finds out above-mentioned the key reasons causing these problems and proposes manymeasures to improve the water quality, for example,control the proportion of additional quantity of water and theleaking water,softening water system and added drug against the bacteria.Through overall analysis and studying,author thinkes that evaporating cooler will not produce the legion disease.

关 键 词:蒸发冷却器 水系统 工程应用 空调 软化 水垢 补水 水质问题 水作 环境 

分 类 号:TU831[建筑科学—供热、供燃气、通风及空调工程]

 