电力交流接地网损坏原因调研与分析  被引量:25

Investigation and Analysis on Damage Reasons of AC Electric Power Grounding Network

在线阅读下载全文

作  者:蔡崇积[1] 

机构地区:[1]武汉高压研究所,湖北省武汉市430074

出  处:《电力设备》2005年第4期20-22,共3页Electrical Equipment

摘  要:通过对电力交流接地网损坏原因进行调研发现,接地网现场出现的主要问题是接地网腐蚀、接地引下线截面偏小以及接地体之间连接不良,而出现这样问题的关键环节却在设计(标准)和施工质量管理上。文章对现场暴露的接地网腐蚀、接地引下线截面偏小和接地体之间连接不良3个方面主要技术原因进行了技术分析。指出,要提高接地网的可靠性,就应制定或修订相关标准。According to the investigation of damaging reasons for AC electric power grounding network, the major problems occurred on - the - spot of grounding network are corrosion of grounding network, little section of grounding down lead and bad connection between grounding bodies, and the crucial link for such problems is on management of design and construction quality. The technical a-nalysis for the reasons from three aspects mentioned above was carried out. It is pointed out that the relative standards should be established or revised to raise the reliability of grounding network.

关 键 词:电力交流接地网 接地体 接地带 接地引下线 损坏原因 

分 类 号:TM727.2[电气工程—电力系统及自动化] TM862

 