机构地区:[1]中国科学院电工研究所,北京市海淀区100080
出 处:《中国电机工程学报》2005年第11期101-106,共6页Proceedings of the CSEE
摘 要:国产大型汽轮发电机,很难做到24kV电压等级。电压高,定子绕组槽内电场分布的改善及耐电晕等技术处理难度大。该文采用理论计算与模型实验两方面的仿真手段,详尽地分析了蒸发冷却方式下形成的气、液、固三态绝缘体系的耐电晕、耐击穿的可靠性,提出一种适合于该冷却方式的、应用于高电压等级的新型定子绝缘结构,系统地研究了结构的绝缘特点及规律,并得出这一新型绝缘体系对24kV电压等级是可行的结论。It is very difficult for 24kV rated voltage large turbo-generator to be manufactured in China. Because under high voltage, the technology to improve electric field distribution of stator coil in slot and to against corona in slot is hard to finish. By calculative and experimental simulation, this paper analyzed in detail the three-state insulative system consisted of gas, liquid, and solid formed by evaporative cooling mode, including the reliability of its anti-corona and anti-breakdown . This paper offers a new kind of stator insulation structure that is suitable to evaporative cooling mode and can be applied to high voltage level. After a series of researches on insulative characters and laws of the new structure, a conclusion that the new insulative system is feasible to 24kV rated voltage is arrived.
关 键 词:绝缘结构 发电机定子 蒸发冷却 大型汽轮发电机 电压等级 冷却方式 绝缘体系 技术处理 电场分布 定子绕组 模型实验 理论计算 耐电晕 可靠性