检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]山西电力局中调所继电保护科 [2]山西电力局电网处
出 处:《电力学报》1995年第3期12-16,共5页Journal of Electric Power
摘 要:本文论述了数字型继电保护装置中的程序存储器EPROM在现场运行中出现的问题和装置内逆变电源问题,指出现有的装置中大量使用的主要检错手段ROM字节和不能作为运行中检测程序正确性的唯一手段,而应辅之以CRC等检错率较高的方法。110KV及以下电网的数字保护装置内,应配置双逆变电源。This artical discusses the data-change proleom in the EPROM that is widely used to syore progam in digital protective relay when the relay is in running state. Points out that it must not bethe only way to check and proof the program in running state by the sum of the EPROM byte, some other better way such as CRC(Cyclic Redundancy Check)must be used when check and proof the program in dynamic state. It is also a severc problem when the relay powered by only on. DC-DC power deivce in the protective relay,suggests that double DC-DC power device should be used in the relays when the high volrage (110KV or lower voltage) line protected by only one relay.
分 类 号:TM774[电气工程—电力系统及自动化] TM58