检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]福建省福清市供电有限公司,福建福清350300 [2]上海交通大学电子信息与电气工程学院,上海200240
出 处:《水电能源科学》2006年第1期15-18,共4页Water Resources and Power
基 金:上海高校优秀青年教师后备人选科技基金资助项目(04YQHB020);许继电力科技基金资助项目
摘 要:利用不同线路发生单相接地短路时,故障线路与非故障线路零序电流相位差值和故障位置的数学关系作为识别依据,提出适用于平行双回线路的零序距离保护新判据。新方法具有受两侧电源角度及受负荷、系统运行方式影响小的特点。大量ATP仿真试验证明,新方法对于双回线出现的单相接地故障具有足够的灵敏度。A double lines distance relay based on the zero sequence components is presented.By study,we can know that when one-phase ground fault happens on the line,more far the fault location is from where relays place,more less is the difference between the two zero sequence currents,when one-phase ground fault happens on the other line,more far the fault location is from where relays place,more is the difference between the two zero sequence currents..So the line which the one-phase ground fault take place can be distingusted.It has the characteristics of fault component relays such as being immune to the load and the system operating mode and the zero sequence components required by the relay can be easily acquired and available for a long time.The theoretic analysis and ATP-EMTP simulation results show the distance relay has excellent performance in detecting one-phase ground fault for double lines.
关 键 词:平行双回线 单相接地 距离保护 零序电流 故障分量
分 类 号:TM773[电气工程—电力系统及自动化]