检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]武汉大学电气工程学院,武汉430072 [2]中国地质大学计算机科学与技术系,武汉430074
出 处:《高电压技术》2006年第2期98-100,103,共4页High Voltage Engineering
摘 要:为更好地应用电力有源滤波器技术,通过最优化数学模型的建立介绍了瞬时无功功率理论的基本内容,所谓瞬时有功电流即保证三相瞬时总能量不变而三相传输损失最小的电流;空间基变换证明,电压和电流瞬时值从a b c三相变换到αβο三相为正交变换,说明三相三线制系统或无零序电压电流时三相到两相变换的合理性,从而将αβ变换与d q变换联系起来。最后指明系统电压畸变时不宜用基于该理论的谐波检测和无功补偿方法。This paper introduces the Instantaneous Reactive Power Theory; clarifies that the instantaneous active current is the current which makes the three-phase transmission power loss least in the condition of keeping the three-phase instantaneous power constant according to the optimal math model; tries to prove that the transformation of voltage and current instantaneous values from a b c three phases into αβ three phases is orthogonal transform, thus the transform from three-phase into two-phase is rational for the three-phase three-wire system or the system without zero-phase voltage and current; and relates αβ transform with d q transform, points out the method for harmonic detection and reactive power compensation based on this theory is not applicable when the voltage is distorted.
分 类 号:TM714[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.147