Floating-roof steel tanks under harmonic settlement: FE parametric study and design criterion  被引量:1

Floating-roof steel tanks under harmonic settlement:FE parametric study and design criterion

在线阅读下载全文

作  者:赵阳 曹庆帅 谢新宇 

机构地区:[1]Department of Civil Engineering, Zhejiang University, Hangzhou 310027, China

出  处:《Journal of Zhejiang University-Science A(Applied Physics & Engineering)》2006年第3期398-406,共9页浙江大学学报(英文版)A辑(应用物理与工程)

基  金:Project supported by the National Natural Science Foundation of China (No. 50208017) and the Scientific Research Foundation forReturned Overseas Chinese Scholars, Ministry of Education (No.J20040157), China

摘  要:Large vertical steel tanks for fluid storage are usually constructed on soft foundations, so it is not surprising that the tank wall will settle unevenly with the settlement of the foundation, thus inducing deformations and stresses in the tank. This work investigates the linear static behavior of floating-roof tanks under harmonic settlement through finite element (FE) analyses. The influences of the radius-to-thickness ratio, the height-to-radius ratio and the wind girder stiffness on the structural behavior are first analyzed. Comparisons between the circumferential stresses in the wind girder and the vertical stresses in the tank bottom are then made. The displacement and the stress along the tank height are also discussed, and the concept of tank division along its height is presented. Finally, a design approximation for the radial displacement at the tank top is developed based on FE results, and a settlement criterion based on the top radial displacement is proposed which can be used in practical design.Large vertical steel tanks for fluid storage are usually constructed on soft foundations, so it is not surprising that the tank wall will settle unevenly with the settlement of the foundation, thus inducing deformations and stresses in the tank. This work investigates the linear static behavior of floating-roof tanks under harmonic settlement through finite element (FE) analyses. The influences of the radius-to-thickness ratio, the height-to-radius ratio and the wind girder stiffness on the structural behavior are first analyzed. Comparisons between the circumferential stresses in the wind girder and the vertical stresses in the tank bottom are then made. The displacement and the stress along the tank height are also discussed, and the concept of tank division along its height is presented. Finally, a design approximation for the radial displacement at the tank top is developed based on FE results, and a settlement criterion based on the top radial displacement is proposed which can be used in practical design.

关 键 词:Steel tanks Floating-roof Differential settlement Harmonic settlement Finite element analysis Design criterion 

分 类 号:TU476[建筑科学—结构工程]

 