作 者:冯文如[1] 钟嶷[1] 刘世强[1] 江思力[1] 周明辉[1] 宋宏[2]
机构地区:[1]广州市疾病预防控制中心,广州510080 [2]中山大学公共卫生学院,广州510080
出 处:《热带医学杂志》2006年第3期322-324,共3页Journal of Tropical Medicine
摘 要:目的研究含氯消毒剂对冷却塔军团菌的现场杀菌效果。方法选择一大型冷却塔,分别进行两种消毒方式:一次添加高浓度氯消毒剂后(冲击法),维持加氯和不维持加氯,并在当天和一周后检测冷却塔水中军团菌的浓度。结果持续加氯,保持游离余氯在(0.38±0.23)mg/L,军团菌浓度变化不大,未检出或保持低浓度(0.85±1.52~0.81±1.56)cfu/ml;不持续加氯,军团菌持续上升,一周后增加100~1000倍以上(0.12±0.11~322.22±130.17)cfu/ml。结论维持加氯的消毒方法对冷却塔军团菌的消毒效果较好。Objective To evaluate the bactericidal effect of chlorine in killing Legfonella in water cooling towers. Methods A large cooling tower was selected in this study. Two different protocols of disinfection were evaluated: (1) by keep on adding the disinfectant chlorine and (2) by adding chlorine once a week. The number of Legionella in the cooling water was determined daily. Results In the first protocol, when the concentration of available chlorine was kept at (0.38±0.23)mg/L,the number of Legionella did not change obviously (0.85±1.52- 0.81±1.56)cfu/ml. In the second protocol,when chlorine was added once a week, the number of Legionella was increasing. The concentration of LegioneUa was found to increase 100-1 000 times(0.12±0.11-322.22±130.17) cfu/ ml at 1 week after the experiment. Conclusion Maintaining the concentration of chlorine in water cooling tower is essential in controlling the growth Legionella.