间隔层保护测控装置防误操作实现方法  被引量:60

Implementation of Mai-operation Proof on Platforms of Relay and Control Units Between Bays

在线阅读下载全文

作  者:孙一民[1] 侯林[1] 揭萍[1] 唐成虹[1] 

机构地区:[1]国电自动化研究院/南京南瑞集团公司,江苏省南京市210003

出  处:《电力系统自动化》2006年第11期81-85,共5页Automation of Electric Power Systems

摘  要:间隔层保护测控装置防误操作已成为变电站综合自动化系统的必要功能。文中阐述了一种在监控后台用脚本语言编写五防规则,在间隔层保护测控装置安装脚本引擎,下装五防规则库到装置,从而实现间隔层保护测控装置防误操作的方法。详细描述了脚本语言和脚本编译器的设计方法,在监控后台实现五防规则的编译和安全测试。The implementation of mal-operation proof operation within or between bays has become an important function of the substation automation system. A mal-operation proof method is described that consists in writing proofing rules at the workstation, equipping relay and control units with a script virtual machine, and downloading proofing rules to units. The design of a script language and its virtual machine is explained in detail. The compiling and security test of the proofing rules are realized by the back-end system.

关 键 词:保护测控装置 防误操作 五防规则 脚本语言 脚本引擎 

分 类 号:TM764[电气工程—电力系统及自动化] TM774

 