机构地区:[1]武汉科技大学城市建设学院,湖北武汉430070
出 处:《武汉科技大学学报》2006年第3期289-292,共4页Journal of Wuhan University of Science and Technology
基 金:湖北省教育厅科研资助项目(D200511009)
摘 要:采用依次关闭各支路,然后计算未关闭支路流量的方法,分析和对比异程系统与同程系统的稳定性。结果表明,异程系统从离热源最近的支路到最远支路,稳定性依次变差;同程系统的稳定性具有对称性,网路中部的支路稳定性最差,越往两端,支路的稳定性越好;从总体上讲,同程系统的稳定性差于异程系统。By employing the method that shuts each subcircuit, the paper analyzes and compares the hydraulic stability of direct return system (DRS) and reverse return system (RRS). The results show that : from the subcircuit that is furthest to the heat source to the nearest one, the stability of DRS becomes gradually worse; the stability of RRS is symmetrical, with the subcircuit in the middle of the pipe-network having the worst stability, while, the nearer to the two ends, the better the stability of the subcircuits is. It' s concluded that the overall'stability of RRS is inferior to DRS.
分 类 号:TU834.3[建筑科学—供热、供燃气、通风及空调工程]