CMP桌面工位空调的气流组织与微环境评价  被引量:3

Air distribution and microenvironment evaluation of CMP desktop task air conditioning

在线阅读下载全文

作  者:郑国忠[1] 荆有印 

机构地区:[1]华北电力大学

出  处:《制冷与空调》2006年第3期33-37,共5页Refrigeration and Air-Conditioning

摘  要:采用k-ε三维湍流模型对安装电脑显示器风口(computer monitor panel,CMP)桌面式工位空调系统的一典型办公室工作区微环境进行数值模拟,对3种送风速度下工作区及人体周围的温度场、速度场以及人体吹风感(draught rating,DR)和预期不满意百分率(predicted percentage of dissatisfied,PPD)进行分析与研究。研究结果表明,工位空调室内温度呈现分区分布,工位送风效率高,可以实现总体节能,在合适的工位送风速度下,可以为办公人员提供较佳的工作环境。Numerically simulates the microenvironment of a typical workstations with computer monitor panel (CMP) task air condition system by k-ε 3-D turbulent flow. Analyzes and studies the temperature and velocity distribution, draught rating (DR) and predicted percentage of dissatisfied (PPD) of the room and workstation in three supply air velocities. The results show that the room temperature presents partition distribution and the task conditioning has good air-supply efficiency, which can achieve total energy conservation. And results also show that the task air conditioning can provide a good working environment for officer when the supply velocity is well designed.

关 键 词:工位空调 电脑显示器风口 微环境 气流组织 数值模拟 

分 类 号:TU831.4[建筑科学—供热、供燃气、通风及空调工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象