光纤复合架空地线(OPGW)结构设计中的几个问题  被引量:9

Several Issues in Design Structures for OPGW

在线阅读下载全文

作  者:曹佩荣[1] 曹君[2] 曹锦[3] 

机构地区:[1]江苏省电力公司,南京市210018 [2]国电南京自动化研究院,南京市210024 [3]解放军理工大学,南京市210007

出  处:《电力建设》2006年第8期6-12,共7页Electric Power Construction

摘  要:OPGW作为避雷线,遭受雷击不可避免。为避免落雷电弧烧坏光纤,国内外不少厂家在内、外层绞丝之间或与光单元之间设计留有一定空隙,给雷电流沿线传播在间隙上形成电位差、产生电弧创造了条件,一旦电弧产生,15~30V就能维持,其产生的热量,使OPGW温度上升、强度下降,形成断股。因此,OPGW雷击断股的主要原因是结构设计问题。并提出了解决方法和措施。As the lightning wire, OPGW cant be avoided from lightning. In order to prevent the optical fiber from burning from the lightning arc both domestic and foreign manufactures have leave a gap between the internal and external strands and optical unit to a certain extent, which forms a potential difference at the gap for transmission of lightning current along the wire and creates a condition of arc generation. So the main causes for OPGW strand breakage form lightning are the structural design problems. The author gives out the solution and measures.

关 键 词:OPGW 断股 结构设计 

分 类 号:TN752[电子电信—电路与系统]

 