大型变压器局部放电测量及其需要注意的几个问题  被引量:15

Measurement and Several Problems in Partial Discharge Test of Large Transformers

在线阅读下载全文

作  者:张柯[1] 余晓鹏[1] 王玉学 

机构地区:[1]河南电力试验研究院,河南郑州451000 [2]许昌市电业局,河南许昌461000

出  处:《高压电器》2006年第5期393-394,396,共3页High Voltage Apparatus

摘  要:介绍了变频电源的工作原理、试验接线,对现场试验中应该注意的一些突出问题进行了分析,并根据现场经验提出具体解决方法。利用这种加压方式顺利完成了国内第1台三相一体、电压等级500kV、容量720MV·A大型电力变压器局部放电现场测量。这是采用该方式对高电压、大容量变压器局部放电现场测量的一次有益的尝试。In this paper, the operation principle and the test connecting of frequency conversion power supply are introduced in detail. Some notable problems in field' test are analyzed, and the concrete solutions are also put forward according to field practicing. Based on this method, the partial discharge test for the first domestic transformer, three phase in one tank, 500 kV 720 MV·A, is accomplished successfully. This is also a beneficial attempt about partial discharge field measurement of high voltage, huge capacity transformer.

关 键 词:变压器 局部放电 补偿 干扰 

分 类 号:TM835[电气工程—高电压与绝缘技术]

 