超高压变电站导线力学计算与试验  被引量:2

Mechanical Calculation and Test on Conductor of Extra High Voltage Substation

在线阅读下载全文

作  者:陈井彦[1] 张嘉伟[1] 陈建华[1] 赵强[1] 

机构地区:[1]东北电力大学,吉林吉林132012

出  处:《吉林电力》2006年第5期7-9,共3页Jilin Electric Power

摘  要:500 kV超高压变电站设备损坏原因是因为导线截面较大,变电站设备间的距离又较短,而存在着一定的抗弯刚度,以及导线按一般悬链线计算的不合理性。通过荷载试验,建立了多元回归方程,为端子设计提供了新的计算方法。This paper introduced that the reason of the equipments damage in EHV substation was because of large cross section of the conductor, as well as the short distance between equipments of the substation. It is also resulted by the bending rigidity and the unreasonable theory of the general catenoid calculation of the conductor. We have established the data regression equation, which is based on load experimene, and provided new calculation method for terminals on EHV substation design.

关 键 词:导线 超高压变电所 载荷 端子 

分 类 号:TM63[电气工程—电力系统及自动化] TM24[一般工业技术—材料科学与工程]

 