摘  要:比较了两种回归温差下一级侧机组的启停周期、系统供暖特性等。现场测试结果显示,加大回归温差,可以使一级侧机组小时启停频率降低至3h-1以内,而系统能效比仍保持较高。分析了加大回归温差对末端环路水温的影响。讨论了最大回归温差的确定方法。Compares the start-up period and the heating characteristics of the first stage machines under two regress temperature difference. The field test results show that the first stage machines operating with large regress temperature difference will lower the start-up frequency to three times per hour and keep up higher energy efficiency. Analyses the effect of the enlarging regress temperature difference on the water temperature of terminal loop. Discusses the method for determining the maximal regress temperature difference.

关 键 词:双级耦合热泵 中间水环路 一级侧机组 回归温差 