摘 要:讨论工位空调末端装置的稳定性研究时,建立了其空调系统各环节模型,通过MATLAB软件simulink工具箱为平台建立其计算机仿真系统,比较分析了常用的末端装置上优劣性。通过仿真分析变风量末端测量温度的时间常数对变风量系统的影响,结果显示,若通过降低变风量末端测量区域温度的时间常数使之在300 s以内,就可以在工位空调变风量系统中采用压力有关的末端以降低整个变风量系统的造价。As to study terminal stability, TAC system model is established, and simulink toolbox of MATLAB software has been used to establish the terminal computer simulation system as the platform, and then their quality is compared and analyzed. However, by analyzing the influence on the time-constant of terminal survey temperature to VAV system, It was discovered that if the time-constant of temperature is within 300 seconds, then the pressure related terminal may be suitable in VAV system which can cause cheap cost.