用CO_2-空气换热器冷却燃机进口空气的实验研究  

Experimental Study on Gas Turbine Inlet Air Cooling with CO_2-air Heat Exchanger

在线阅读下载全文

作  者:何明勋[1] 陶正良[1] 江薛麟[1] 张健[1] 

机构地区:[1]上海理工大学,上海200093

出  处:《流体机械》2006年第12期10-12,4,共4页Fluid Machinery

摘  要:对CO2-空气换热器进行了研究和试验,得出了该类型换热器的传热和阻力特性曲线以及温度场分布规律。实验发现空气经冷却后压力损失比未冷却时有5%~10%的减小,而传热因子j和阻力因子f,随换热条件的改变而基本保持不变。将实验结果与参考文献数据相比较,发现阻力因子f与参考文献基本吻合,而传热因子j有所减小。CO2-air heat exchanger was studied and tested and the heat exchanger' s performance curve, relationship of factor j and f ,reynolds number and the flow field distribution were got. Results show that the pressure drop is 5%- 10% lower in cooling model than no heat exchange, and there is no much change about factor j and f despite of the heat transfer condition. When compared with the reference datum, the measured factor f coincides with it very well, and factor j is slightly lower than it.

关 键 词:紧凑式换热器 板翅式换热器 燃气轮机 进口空气冷却 CO2 

分 类 号:TK172[动力工程及工程热物理—热能工程] TK174

 