燃油泵联锁切换试验研究  

TEST STUDY ON INTERLOCK AND SWITCH OVER OF FUEL-OIL PUMP

在线阅读下载全文

作  者:刘文胜[1] 王达峰[1] 张永军[1] 

机构地区:[1]浙江省电力试验研究院,浙江杭州310014

出  处:《热力发电》2007年第1期77-79,共3页Thermal Power Generation

摘  要:燃油泵变频启动初期油泵出力低,难以维持燃油系统压力。对此,通过燃油泵变频和工频联锁切换比较试验,对切泵过程中燃油压力变化进行对比分析,结果表明,燃油泵采用变频切换方式会导致燃油系统跳闸,而采用工频切换方式则可避免此类问题发生。In the initial stage of frequency conversion to start the fuel -oil pump, the output capacity of said pump has been lowered, being difficult to maitain the pressure in fuel oil system. For this, the pressure variation of fuel oil in the process of switching the pump over has been compared and analysed through comparison test of interlock and switch over under frequency conversion and power frequency of the fuel oil pump, Results show that the switch over mode adopted by the fuel oil pump under frequency conversion can lead the fuel oil system to trip, but the switch over mode under power frequency can avoid the fuel oil system to trip.

关 键 词:火电厂 燃油泵 变频 工频 联锁 OFT 试验 

分 类 号:TK323[动力工程及工程热物理—热能工程]

 