35kV架空送电线路防雷用并联间隙研究  被引量:113

Study on Shunt Gap Lightning Protection for 35kV Overhead Transmission Lines

在线阅读下载全文

作  者:陈维江[1] 孙昭英[1] 王献丽[1] 李庆余[1] 颜湘莲[1] 王风雷[2] 李红[2] 王松虞[2] 王增志[2] 张文军[2] 

机构地区:[1]中国电力科学研究院,北京市海淀区100085 [2]北京电力公司,北京市西城区100023

出  处:《电网技术》2007年第2期61-65,共5页Power System Technology

摘  要:为解决35kV架空送电线路的雷击问题,提出采用并联间隙防雷保护方案,分析了其保护原理,设计了35kV线路防雷用并联间隙的结构尺寸;对并联间隙试品进行了大量的雷电冲击和工频电弧试验,结果表明并联间隙能有效保护绝缘子串和导线免于雷击引起的工频续流电弧的烧蚀;计算了带并联间隙线路的雷击跳闸率,建议将3片绝缘子增加为4片,加装并联间隙不会引起线路跳闸率增加。To solve the faults caused by lightning stroke in 35kV overhead a'ansmission lines, it is proposed to use shunt gap as the lightning protection. The protective principle of shunt gap is analyzed and the structure and structural Sizes of shunt gaps for 35kV overhead transmission lines are designed. A lot of lightning impulse and power frequency arcing tests are performed with shunt gap test specimen, and test results show that shunt gap can effectively make insulator strings and wires exclusive from ablation of power frequency arc incurred by lightning stroke. The fightning trip-out rate of 35 kV overhead lines with shunt gap is calculated, on this basis the authors recommend that when shunt gaps are equipped in 35 kV transmission lines, in order to restrict the increase of the lightning trip-out rate the number of insulator pieces in a single string should be changed from original three pieces into four pieces.

关 键 词:35 kV架空送电线路 防雷保护 并联间隙 雷击跳闸率 

分 类 号:TM862[电气工程—高电压与绝缘技术]

 