摘 要:针对《建筑设计防火规范》(GB50016—2006)和《高层民用建筑设计防火规范》(GB50045—95)(2005年版)中消防水池吸水井设置要求不一致的问题,分析了吸水井与建筑物的安全距离,介绍了消防水池与吸水井间连通管的设置方式,推导了低位连通管设置时管径的计算公式,提出了连通管管径不应小于150mm的建议。Aimed at the conflicting requirements for installation of the inlet well for fire pool between the Code of Design on Building Fire Protection and Prevention (GB 50016 -2006) and the Code for Fire Protection Design of Tall Buildings ( GB 50045 - 95 ) ( edition 2005 ), the safe distance from the inlet well to the building was analyzed, the installation way of connection pipe between the fire pool and the inlet well was introduced, the calculation formula for the pipe diameter during installation of low-level connection pipe was derived, and the suggestion that the diameter of connection pipe should not be less than 150 mm was presented.