国产12kV铠装式金属封闭开关设备技术隐患分析与对策  被引量:13

Analysis and Countermeasures of the Technical Potential Problems in Domestic 12 kV Metalclad Switchgears

在线阅读下载全文

作  者:钟家喜 金李鸣[2] 徐彬 李向军 

机构地区:[1]衢州市电力局,浙江衢州324002 [2]浙江省电力试验研究院,浙江杭州310014 [3]浙江华电器材检测研究所,浙江杭州310015 [4]金华市电力局,浙江金华3210001

出  处:《高压电器》2007年第3期232-234,236,共4页High Voltage Apparatus

摘  要:通过对两起国产12 kV铠装式金属封闭开关设备烧毁故障原因的分析和总结,指出目前运行的许多国产12 kV铠装式金属封闭开关设备存在结构性弱点,容易在天气骤变过程中出现凝露,发生绝缘闪络故障和扩大事故范围,并明确提出了解决对策和建议。同时建议制造企业和电力用户重视早期国产12 kV铠装式金属封闭开关设备的整改问题,以达到控制绝缘故障和杜绝“火烧连营”事故的发生。This paper analyzed the fault reason of two domestic 12 kV metalclad switchgears' bum out, pointed out the structure shortcomings of domestic 12kV enclosed switchgears in service. Easy produce vapor condensation when weather sudden change, lead to insulation flashover fault and enlarge accident range. The countermeasures were proposed, and manufacture factory and power user were suggested to pay attention to rectification of switchgears in early stage, so as to control even eliminate insulation fault.

关 键 词:铠装柜 技术隐患 分析 对策 

分 类 号:TM564[电气工程—电器]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象