检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:彭梦珑[1] 黄敬远[1] 丁力行[1] 杨中[1]
机构地区:[1]中南大学能源科学与工程学院
出 处:《建筑科学》2007年第6期37-40,共4页Building Science
摘 要:准确计算空调负荷是进行地下建筑通风空调系统设计的重要环节,空气和岩壁的对流换热属于第四类边界条件,传统编程计算十分复杂。本文使用Fluent软件对洞室岩壁的非稳态传热进行了计算。根据实例计算得出:间歇通风条件下岩壁热流通量达到稳定所需的时间约为1个月,并比较了不同风速和不同岩体材料时,洞室壁温和室温随时间的变化状况,为深埋地下洞室岩壁的热负荷计算提供了参考。Precise computation of cooling load is important for air-conditioning system design. Heat transfer between air and rock wall belongs to the forth boundary condition, and conventional computation programs are always complicated to use. In this paper, using the software of Fluent, unsteady heat transfer of cavity wall was calculated. Based on the example, it was observed that the wall-flux was steady after one month under intermittent ventilation condition. In addition, the characteristics of wall temperature and temperature variation trend under the conditions of different wind speeds and rock materials were analyzed. The results could be useful for the computation of heating load of cavity wall in deeply buried building.