检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:周德元[1]
机构地区:[1]华夏电力公司,福建厦门361026
出 处:《热力发电》2007年第5期35-37,共3页Thermal Power Generation
摘 要:从发电机转子水冷系统设计、安装和运行维护入手,详细分析了嵩屿电厂二期300 MW双水内冷发电机转子出水支座甩水原因,认为主要由于出水支座内水位太高和风压过大、转子卸水槽错位造成。对此,提出了改进方案,实施后彻底消除了甩水现象。starting with the system design, equipment installation, and maintenance in operation of the water cooling rotor in generator, the causes leading to water throw- off from water - discharging susupport of the rotor in dual internal water cooling 300 MW generator in secondary - phase project of Songyu Power Plant have been analysed in detail. After suggesting and implementing the improvement scheme, the water throw- off phenomenon has been thoroughly eliminated.
正在载入数据...