换流站阀冷却系统主水泵电机发热分析  

Heat Analysis of Main Pump Motor of Valve Cooling System in Converter Station

在线阅读下载全文

作  者:郝江涛[1] 郭树永[1] 田兴旺[1] 

机构地区:[1]中国南方电网超高压输电公司天生桥超高压局,贵州兴义562400

出  处:《电机与控制应用》2007年第8期50-52,共3页Electric machines & control application

摘  要:天生桥换流站阀冷却系统主水泵电机相继出现三次发热故障。通过对电机解体分析,发现电机发热是由于轴承"跑外圆"引起。为了解决轴承"跑外圆"问题,针对进口的西门子电机结构特点进行分析,采用了一种新的处理方法。该方法简单实用,操作性强,经过实际应用,验证了该方法的可行性和有效性。The main pump motor of valve cooling system in Tianshen Bridge converter station suffer from the successive excessive heating fault for three times, the motor' s disassembly and analysis show that the bearing running on the outer circle is the reason. Based on characteristic analysis of export SIEMENS motor, a new processing method is proposed. This method has advantages of simple and practical, easy operation, and its feasibility and validity is proven by actual application.

关 键 词:阀冷却系统 水泵电机 电机发热 

分 类 号:TM301.41[电气工程—电机]

 