检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]华东电网有限公司,上海市黄浦区200002 [2]华东电力试验研究院,上海市虹口区200437
出 处:《电网技术》2007年第19期47-51,共5页Power System Technology
摘 要:对华东电网500kV线路发生的污闪事故分析表明,爬距不足和绝缘子伞型不合理是造成线路污闪的最主要原因。根据污闪事故分析,以及为确认线路的安全运行状况,对不同串型、不同形式500kV线路绝缘子串进行了不同污秽度下的污秽试验,得到了不同试品的污耐压曲线,试验结果为500kV线路的污秽外绝缘配置以及正确选型提供参考依据。在此基础上,通过总结华东电网超高压线路的运行经验,并结合试验研究和实际工程应用的基础,研究了各种绝缘子积污特性和爬距有效利用系数,对华东电网500kV线路提出了合理的外绝缘配置。The results of analysis on pollution flashover accidents occurred in 500kV transmission lines of East China Power Grid show that insufficient creepage distance and irrational shed profiles of insulators are the principal reasons to cause pollution flashover of transmission lines. According to the analysis on pollution flashover, in order to confirm the secure operation of transmission lines the pollution tests of insulator strings with different types and different forms for 500kV transmission lines under different pollution extents are conducted and the withstand voltage curves of different specimens under polluted conditions are obtained. The test results are available for reference to the configuration of external insulation as well as to correct selection of shape and arrangement of insulator strings for 500 kV transmission line. On this basis, by means of summarizing operational experiences of UHV transmission lines in East China Power Grid and combining with experimental investigations and practical engineering applications, the contamination accumulation characteristic and creepage distance utilization coefficients of various insulators are researched, then reasonable external insulation configuration for 500 kV transmission lines in East China Power Grid are recommended.
关 键 词:输电线路 外绝缘 污闪 积污特性 绝缘配合 爬距
分 类 号:TM853[电气工程—高电压与绝缘技术]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.147