宜都蔡家冲换流站550kV GIS缺陷分析  被引量:9

Defect Analysis of 550 kV GIS of Yidu Caijiachong Converter Station

在线阅读下载全文

作  者:陈隽[1] 卢军[1] 阮羚[1] 种芝艺 邹军峰 汪林清 

机构地区:[1]湖北省电力试验研究院,武汉市430077 [2]国网直流工程建设有限公司,北京市100005 [3]湖南电力建设监理咨询有限责任公司,长沙市410007

出  处:《电力建设》2007年第11期22-24,共3页Electric Power Construction

摘  要:宜都蔡家冲换流站GIS安装调试期间发现多起设备缺陷。通过交流耐压试验及局部放电测量发现隔离开关绝缘拉杆存在质量缺陷,更换合格绝缘拉杆后试验通过。断路器解体检查及时发现了内部缺陷,避免了事故发生。进行气体泄漏检查时发现多处气室轻微漏气。气体湿度测量发现超过厂家控制标准,需要进行复测。During the installation and testing process of Yidu Caijiachong Converter Station GIS, several device defects are identified. Through AC voltage test and local discharge measurement, separating switch insulation rod quality defects are found, and it passed test after replaced with qualified one. Breaker internal defects are discovered during disassembling examination, which avoids accident. Minor leaks in several gas chambers are found in leak test. Measurement indicates that gas humidity exceeds manufacturer' s limit and requires recheck.

关 键 词:GIS 设备缺陷 绝缘拉杆 断路器 气体泄漏 湿度超标 

分 类 号:TM595[电气工程—电器]

 