深圳市某政府办公大楼空调冷却塔的节能诊断  被引量:1

Diagnosis for Energy Efficiency of Cooling Towers of Shenzhen Government Office Building's Air-conditioning System

在线阅读下载全文

作  者:资晓琦[1] 何天祺[1] 刘俊跃 朱磊[1] 

机构地区:[1]重庆大学城市建设与环境工程学院 [2]深圳市建筑节能重点实验室

出  处:《建筑热能通风空调》2007年第5期45-48,共4页Building Energy & Environment

基  金:美国能源基金会推进中国夏热冬暖地区建筑节能标准的实施"深圳市综合示范项目"(G-0609-08544)

摘  要:为了实现中央空调系统的节能,对大楼的空调冷却塔运行性能进行了测试。通过对制冷机冷却水出口温度、冷却塔出口水温和室外气象参数的观察记录,由冷却塔效率计算公式求得冷却塔的效率。测试发现,该大楼冷却塔效率整体偏高,主要是因为风机功率偏大保证了较高的气水比。最后分析了对冷却塔效率的影响因素,提出了改造建议。In order to improving energy efficiency of central air-conditioning system, the performance of cooling towers in Shenzhen Office Building has been tested. Based the records of cooling water outlet temperature, the outlet water temperature and outside weather parameter, the efficiency of the cooling towers could be calculated by the formula. For the greater power of the fans guaranteed the high ratio of air and water, the cooling towers has high efficiency. At the same time, the impacts of cooling tower's efficiency were analyzed and some advices were presented to improve the cooling tower's efficiency.

关 键 词:节能诊断 冷却塔 气水比 

分 类 号:TU831.8[建筑科学—供热、供燃气、通风及空调工程]

 