试解读PEN线分开时接母排的先后次序  

Unscrambling the Precedence for Busbar Connection at Separate PEN Conductor

在线阅读下载全文

作  者:李荣茂 

机构地区:[1]中船第九设计研究院有限公司,上海市200063

出  处:《建筑电气》2007年第12期16-17,共2页Building Electricity

摘  要:国内先前的做法,美国现行的做法,均为先接N线母排。国际电工委员会IEC标准从人身安全角度考虑,PEN线分开时,应先接PE线母排;但对变电所之类大电流场所,则应让电流顺畅地流回电源,且连接板导电不良是小概率事件,故应先接N母排。The previous approach in China, the present approach in USA, are both first connecting the N conductor busbar. The conclusion of IEC (International Electrotechnical Commission) codes is that: considering from the personal safety, when the PEN conductor is separate, the busbar of PE conductor should be connected firstly; but for the high current places such as substation, the current should be made to flow smoothly back to the power supply; in addition, the poor conduction of the connecting board is of small probability event, therefore, N conductor busbar should be firstly connected.

关 键 词:PEN线 PE母排 N母排 先后次序 人身安全 

分 类 号:TM63[电气工程—电力系统及自动化]

 