发电机漏氢标准讨论  被引量:4

Discussion on Generator Hydrogen Leakage Standard

在线阅读下载全文

作  者:谢尉扬 

机构地区:[1]浙江省电力建设有限公司,浙江省宁波市315010

出  处:《电力建设》2008年第2期67-69,共3页Electric Power Construction

摘  要:现行的发电机漏氢标准没有综合考虑发电机机壳内的气体容积、额定氢气压力以及轴端密封形式。发电机漏氢量实际上已经包含了溶解在氢侧密封油回油中且被带走的氢气。当发电机采用单流环密封结构时,由于所溶解的氢气量比较大,应予以考虑。建议发电机漏氢标准以漏氢率为基准,并将单流环密封结构与双流环密封结构区分开。发电机的漏氢量标准可由漏氢率标准换算取得。Current generator hydrogen leakage standard does not take into account of gas volume inside generator case, nominal hydrogen pressure, and shaft seal types. The generator hydrogen leakage actually includes the hydrogen that is dissolved in recovery seal oil on the hydrogen side and being taken away. When single flow seal is used, because of larger hydrogen dissolving, aforementioned effect should be considered. It is recommended that using hydrogen leakage rate as standard and differentiating single flow seal regions and double flow seal regions. Generator hydrogen leakage standard can be obtained from converting hydrogen leakage rate standard.

关 键 词:发电机 漏氢量 漏氢率 标准 

分 类 号:TM311[电气工程—电机]

 