送排风对中庭烟气温度影响的实验研究  

Experiment of effects of supply and exhaust air on smoke temperature in atria

在线阅读下载全文

作  者:王继梅[1] 赵菊[1] 李建国 肖勇全[1] 王封江 薛永明[1] 

机构地区:[1]山东建筑大学 [2]青岛安装建设股份有限公司 [3]山东汇智工程设计有限公司

出  处:《暖通空调》2008年第1期110-113,共4页Heating Ventilating & Air Conditioning

基  金:山东省自然科学基金项目(编号:Y2006F27)

摘  要:通过理论分析得出了无喷淋中庭火源的火焰气流各分区的高度范围及烟气温度随中庭高度的变化趋势。在模型中庭内进行了发烟实验,得到了在自然状态、上送风、下排烟和上送下排状态下烟气温度随模型中庭高度的变化曲线。实验结果与理论结果的对比表明,在湍流区二者偏差不大。Explores the height range of fire source subareas for the atrium without sprinkling devices and the changing trend of smoke temperature with atrium height by theoretical analysis. Obtains the relationship curves of smoke temperature with the height of model atrium by smoke tests under natural ventilation, supply air in upper zone, exhaust smoke in lower zone and combined with upper supply and lower exhaust conditions. A comparison shows that there is minor deviation between the experiment results and theoretical analysis results.

关 键 词:送风 排烟 中庭 烟气温度 

分 类 号:TU831[建筑科学—供热、供燃气、通风及空调工程]

 