加强线路绝缘对220kV变电站绝缘配合的影响  被引量:5

Influence of Strengthening Line Insulation on Insulation Coordination in 220kV Substation

在线阅读下载全文

作  者:徐伟[1] 张大鹏[1] 刘浔[1] 唐程 刘熙 吴国华[1] 

机构地区:[1]华中科技大学电气与电子工程学院,湖北武汉430074 [2]武汉高电压研究院,湖北武汉430074

出  处:《水电能源科学》2008年第2期160-163,共4页Water Resources and Power

摘  要:针对加强线路绝缘能有效减少污闪事故、减小线路反击率但也可能会对变电站的绝缘配合构成威胁的情况,以瑞金220 kV变电站两种不同运行方式为例,建立了基于电磁暂态程序ATP-EMTP的仿真计算模型,计算了加强线路绝缘后雷电侵入波在变电站电气设备上产生的过电压或雷电流,研究了对变电站绝缘配合的影响。仿真计算结果表明,加强线路绝缘不会对该变电站绝缘配合构成威胁。Strengthening line insulation is effective in reducing pollution flashover accident and lowering conversely-attack rates of the lines. But it may cause a threat to current insulation coordination. The numerical simulation calculation models of certain 220 kV substation and transmission lines were established for its two different operating modes by electromagnetic transient calculation program ATP-EMTP. The over-voltage and lightning current generated in the electrical equipments of the substation were calculated and effects of lightning intruding surge on insulation coordination in substation after strengthening line insulation were studied in this paper. The research shows that there is no threat to current insulation coordination if line insulation is strengthened.

关 键 词:雷电侵入波 线路绝缘 绝缘配合 ATP—EMTP 

分 类 号:TM726[电气工程—电力系统及自动化]

 