检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:景敏慧[1] 柳焕章[2] 邓洪涛[1] 许群[1] 张哲[1]
机构地区:[1]南京南瑞继保电气有限公司,江苏省南京市211106 [2]华中电网有限公司,湖北省武汉市430077
出 处:《电力系统自动化》2008年第8期55-58,共4页Automation of Electric Power Systems
摘 要:通过实例分析说明平行双回线路在强磁弱电联系运行方式下,一回线路末端发生高阻接地故障时,非故障线路纵联零序方向保护会误动,而纵联负序方向保护不会误动,提出在使用纵联零序方向保护切除高阻接地故障的保护装置中,增加纵联负序方向保护,退出纵联零序方向保护以防止误动的发生,并讨论了纵联负序方向保护新方案,方案增加负序电抗继电器和负序电流、电压闭锁,并带小延时动作,从而确保平行线之一故障时,非故障线路纵联负序方向保护不会误动,而故障线路发生高阻接地故障时,纵联负序方向保护能带小延时可靠切除故障。Operational experiences indicate that when a high resistance ground fault occurs on one of two parallel double-circuit lines under the strong-magnetic and weak-current operation condition, the pilot zero sequence directional protection of the non- fault line may mal-function while the pilot negative sequence directional protection will not. If a pilot negative sequence directional protection is used to replace the zero sequence one, the mal-function caused by high resistance ground faults can be avoided. A new pilot negative sequence directional protection scheme is also presented, which combines a negative sequence reactance relay, negative sequence current and voltage blocking, and a short time delay. The scheme can avoid mal-function of the protection on the non-fault line and isolate the faulty line reliably.
关 键 词:平行双回线路 纵联零序方向保护 高阻接地故障 纵联负序方向保护 误动
分 类 号:TM86[电气工程—高电压与绝缘技术]