基于行波原理的优化组合故障测距技术  被引量:13

An optimal combined transmission line fault location technique based on travelling wave principles

在线阅读下载全文

作  者:于桂音[1] 陈平[1] 徐丙垠[1] 哈恒旭[1] 

机构地区:[1]山东理工大学电气与电子工程学院,山东淄博255049

出  处:《继电器》2008年第9期11-15,20,共6页Relay

基  金:山东省自然科学基金资助项目(2004ZX26)~~

摘  要:对现代D型双端和A型单端输电线路行波故障测距原理的准确性和可靠性进行了综合评价。在此基础上,提出了基于这两种行波原理的优化组合测距思想,并成功用于实际故障暂态行波分析。与单独的D型或A型行波测距方案相比,本方案的最大优点是能够利用A型行波原理对D型行波原理给出的测距结果进行验证和校正,从而同时提高了测距可靠性和准确性。实际应用表明,优化组合行波测距方案是可行的,并且测距精度得到明显提高。A general appraisal is given to the modern Type D double-ended and Type A single-ended transmisison line fault location principles based on travelling waves in accuracy and reliability. Based on this, an optimal combined fault location idea is presented based on the two types of travelling wave principles, which is applied to the actual fault generated transient travelling wave analysis successfully. Compared with the separate Type D or Type A travelling wave based fault lcoation scheme, the most important virtue of the presented scheme is that the Type D based fault location result can be validated and calibrated by Type A travelling wave principle, thereby both of the location reliability and accuracy are improved. The actual applications show that the presented optimal combined fault location scheme is feasible, and the fault location accuracy is improved evidently.

关 键 词:输电线路 行波 故障测距 全球定位系统 

分 类 号:TM755[电气工程—电力系统及自动化]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象