检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]河南理工大学电气工程与自动化学院,河南焦作454150
出 处:《工矿自动化》2008年第3期19-23,共5页Journal Of Mine Automation
基 金:煤炭青年基金资助项目(117160)
摘 要:煤矿高压电网发生短路故障常导致无选择性越级跳闸,这是井下供电长期存在的安全隐患和技术难题。文章利用小波变换模极大值与行波奇异点的对应关系,准确提取各次行波到达保护安装处的时刻,然后通过实时计算电缆中特定频率下的行波波速,对故障点进行精确定位;利用保护动作时间随故障距离增大而增大的关系,以微机的逻辑判断构建了快速、具有选择性且不受保护间联锁影响的纵向保护系统。The breaker often took place unselective overstep tripping when short circuit fault occurred in mine high-voltage power network, which is a technical problems and potential safety hazard of under-ground power supply existed for a long time. The paper used the correspondent relation between modulus maximum of wavelet transform and traveling wave singularity point to measure time of arriving protection installation of traveling wave, then calculated traveling wave speed under particular frequency of the cable in real time for accurate fault location. It made use of action time of protection increasing with fault distance to construct a fast and selective longitudinal protection system by microcomputer's logic judgment, which is not influenced by protections' interlock.