电网不平衡状态下风电机组运行控制中电压同步信号的检测  被引量:47

Detection of Voltage Synchronization Signals for a Wind Energy Generation System Unbalanced Grid Conditions

在线阅读下载全文

作  者:周鹏[1] 贺益康[1] 胡家兵[1] 

机构地区:[1]浙江大学电气工程学院,杭州310027

出  处:《电工技术学报》2008年第5期108-113,共6页Transactions of China Electrotechnical Society

基  金:国家自然科学基金资助项目(50577056)

摘  要:大型风电机组所联电网并不理想,时有故障发生,给并网风电机组运行控制提出更高要求。为了增强风电机组可靠运行能力,必须对各种故障下电网的频率、相角和幅值进行准确、快速地检测,以便控制系统及时采取应对措施。作为风电机组不对称运行的前期研究,本文在充分研究现有锁相环(PLL)技术的基础上,提出了一种能够同时跟踪电网电压正、负序分量的新型双dqPLL方法,并通过仿真和实验验证了其优越的性能。该方法对电网不对称状态具有较强的检测能力,能为电网不对称故障下风电机组运行控制提供实施依据。Because the connected grid for the high-power wind energy generation systems (WEGSs) is not idealized, malfunction will often happens, which will raise more strict demands on the operation of grid-connected WEGSs. In order to improve the operation stability of the high-power WEGSs, some important information of the unbalanced grid must be investigated. For the sake of detecting the amplitude, phase and frequency of the grid voltage under unbalanced conditions, a new kind of phase-locked loop (PLL), the dual-dq PLL, is proposed and studied in the paper. This dual-dq PLL is proved to possess the advantage of detecting the positive and negative sequence components of the grid voltage simultaneously both by simulation and experiment study. As a preparative research fruit, the suggested dual-dq PLL scheme is capable of offering the basis for the controlling of WEGSs under unbalanced grid conditions.

关 键 词:锁相环 风力发电 电网不对称故障 电压同步信号检测 

分 类 号:TM614[电气工程—电力系统及自动化]

 