检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]东华大学环境科学与工程学院
出 处:《洁净与空调技术》2008年第2期13-17,共5页Contamination Control & Air-Conditioning Technology
基 金:国家自然科学基金(No.50578034);上海市"曙光"计划(No.03SG30)资助项目
摘 要:利用数值方法,模拟了冷却顶板与置换通风联合空调系统下室内空气温度、速度和粒子浓度分布特征。结果指出,这种空调通风方式中,室内垂直温差小,可形成良好的室内热环境、并有较好的热舒适性。对于室内粒子浓度分布,在典型污染高度下,呼吸面高度处粒子浓度较高,但在热泳力的作用下,贴近人体的小范围内粒子浓度明显降低。同时,由于冷吊顶成为粒子汇,房间上部区域的粒子浓度较低。The effect of the indoor air velocity, temperature and particle concentration distributions were investigated by numerical simulating in a room with chilling ceiling and displacement ventilation. The results indicate that small vertical temperature difference in the room can create an acceptable indoor thermal environment and thermal comfort. The results also show that, with contaminant source at the typical height from the floor, the particle concentration at the face height is higher that other positions. But, due to the thermophoretic force, the concentration close to the human model decreases obviously. Similarly, it is easy for particles to deposit onto the surface of chilling ceiling, the particle concentration decreases in the upper zones of the room due to thermophoretic migration.
分 类 号:TU834[建筑科学—供热、供燃气、通风及空调工程]