利用长江水作水源热泵冷热源的探讨  被引量:15

Discuss on using Yangtse River water as heat and cold sources of water source heat pumps

在线阅读下载全文

作  者:王明国[1] 付祥钊[1] 王勇[1] 刘勇[1] 陈金华[1] 臧子旋[1] 

机构地区:[1]重庆大学

出  处:《暖通空调》2008年第4期33-34,82,共3页Heating Ventilating & Air Conditioning

基  金:国家"十一五"课题"水源地源热泵高效应用关键技术研究与示范"子课题三(编号:0219002343030)

摘  要:对重庆段长江水温进行了实测,在仅考虑制冷剂与冷却水、制冷剂与长江水体之间的传热温差影响的情况下,水源热泵机组的性能系数能达到6.4以上,热力完善度大于0.76,认为利用长江水作为水源热泵机组的冷热源具有极大的节能潜力。Measures the water temperature of Yangtse River in Chongqing reach. When only considering the effects of heat transfer temperature difference between refrigerant and cooling water and that between refrigerant and the river water, the coefficient of performance of water source heat pump can achieve to over 6.4 and the thermal perfect efficiency can achieve to over 0.76, Therefore, the use of Yangtse River water as the heat and cold sources of water source heat pumps will have great potential of energy efficiency.

关 键 词:长江水体 水源热泵 冷热源 性能系数 