直流电机接线错误分析与接线要点  被引量:1

Error analysis and method points of DC motor wire connection

在线阅读下载全文

作  者:王雄翔 

机构地区:[1]浙江国华浙能发电有限公司,浙江宁波315612

出  处:《中国电力》2008年第7期79-82,共4页Electric Power

摘  要:直流电机安全运行是发电厂机组安全运行的最后一道保障。基于对直流系统绝缘监测装置原理的分析,国华宁电2B小机直流润滑油泵电机启动时直流母线发"母线异常"报警故障,是由电机接线错误引起的。直流电机线端标识混乱,电机制造厂还是沿用1965年版的标准。介绍并励电机正转接线的2条回路和反转接线的2条回路。The effective operation of the DC motor plays a vital part in ensuring safe operation of a generating unit. Based on the principle analysis of the DC system insulation monitoring device in Ninghai Power Plant, when start-up of DC motor of lubricating oil pump for the 2B mini-generator, the warning of the “bus-bar fault” of DC system was caused by its wrong wire-connection. However, its earlier 1965 edition remains popular in today's electrical machine manufacturer, which makes terminal reference of electrical machine conflict. The two circuits of the shunt-excited machine for positive rotation and negative rotation were introduced.

关 键 词:商流电机 绝缘监测装置 线端标志 电机接线 

分 类 号:TM33[电气工程—电机]

 