10MW高温气冷堆交流安全电源供电的可靠性分析  被引量:1

Reliability Analysis of the Emergency Power Supply System for the 10MW High Temperature Gas-cooled Reactor

在线阅读下载全文

作  者:姚良忠[1] 郭人俊[1] 周世新[1] 

机构地区:[1]清华大学核能技术设计研究院,北京100084

出  处:《高技术通讯》1997年第9期53-58,共6页Chinese High Technology Letters

基  金:863计划资助

摘  要:简单介绍了10MW高温气冷堆(HTR-10)电力系统的设计特点,并用故障树法对HTR-10交流安全母线供电的可靠性进行了定量的理论分析。通过对HTR-10与典型核电站设计方案所对应的安全母线供电的可靠性计算比较表明:HTR-10电力系统是一种既简单,又可靠,且十分经济的新型核动力厂设计方案。In this paper, the features of the emergency power supply system of the 10MW High Temperature Gas-cooled Reactor (HTR-10) are briefly introduced, and the reliability of the emergency power supply system of the HTR-10 is calculated using fault-tree analysis method. The calculating results are compared with those obtained using the standard nuclear power plant design method. All the results show that the emergency power supply system of the HTR-10 is not only with high reliability but also quite simple as well as economic.

关 键 词:高温 气冷堆 电力系统 安全母线 可靠性 

分 类 号:TL424[核科学技术—核技术及应用]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象