具体雷害事故的分析及整改措施  被引量:2

Causes and Counter Measures of a Lightning Accident

在线阅读下载全文

作  者:万欣 姚龙 李景禄[2] 赵新德[2] 胡涛[3] 

机构地区:[1]长寿供电局,重庆401220 [2]长沙理工大学电气与信息工程学院,湖南长沙410076 [3]山西省电力勘测设计院,山西太原030001

出  处:《电瓷避雷器》2008年第4期43-46,共4页Insulators and Surge Arresters

摘  要:针对某化工厂遭受的具体雷害事故,介绍了该化工厂电气系统的现状;从气象条件、防雷系统、接地系统、绝缘配合和内过电压等方面分析了雷害事故发生的原因。提出了防雷害事故的整改措施:①加强防雷措施;②改善接地系统;③改善绝缘配合,更换为绝缘水平较高的6A或6B绝缘;④重新整定合理的零序保护动作值,将3kV电气系统各馈线零序电流动作整定值调整到5A;⑤加强电气设备的绝缘监督及运行维护。通过以上整改,确保了该化工厂电气系统的安全稳定运行。In view of certain lightning accident happened in a chemical plant, the situation of the chemical plant is introduced, the factors caused by lightning accident, such as influence of mete-orological conditions, lightning protection system, grounding system, insulation coordination and influence of switching over-voltage are discussed. In order to run this chemical plant safely, the five improvement factors against lightning accident such as enhancing lightning proof measures, improving earth system, improving insulation coordination by replacing to high insulation level of 6 A or 6 B, installing reasonable zero sequence protective tripping values and enhancing electrical equipment insulation supervises and maintenance should be proved with these measures the reliable running of factory's electric system.

关 键 词:雷害事故 3kV电气系统 防雷措施 

分 类 号:TM862[电气工程—高电压与绝缘技术]

 