变压器涌流对零序电流保护的影响分析  被引量:21

Influence of transformer inrush on zero -sequence current protection

在线阅读下载全文

作  者:方愉冬[1] 徐习东[2] 朱炳铨[1] 

机构地区:[1]浙江电力调度通信中心,浙江杭州310007 [2]浙江大学电气工程学院,浙江杭州310027

出  处:《电力自动化设备》2008年第9期115-118,共4页Electric Power Automation Equipment

摘  要:采用ATP仿真计算与实际分析相结合的方法,分析了单台变压器励磁涌流最大零序分量,以及多台变压器涌流零序分量与主变中性点接地方式的关系,得出:剩磁越大,通过调整合闸角所能取得的涌流零序分量越大,当实际最大剩磁为0.7Bm时,涌流零序分量最大可到0.95IN;多台变压器涌流零序分量与中性点接地变压器台数成正比。结合220kV零序电流保护整定原则,分析了涌流零序分量对220kV零序电流保护的影响,得出它对主变零序电流保护和线路零序电流Ⅰ、Ⅱ、Ⅳ段没有影响,对线路零序电流Ⅲ段和母联保护有不利影响,并提出了运行和整定时需采取的相应措施。With ATP simulative calculation and practical analysis,the maximum zero- sequence inrush current of single transformer,as well as the relationship between the zero- sequence inrush current of multiple transformers and the neutral point grounding mode of main transformer,is analyzed. The conclusions are that,the more the residual flux is,the greater the zero-sequence inrush current obtained by switching angle adjustment will be:when the actual maximum residual flux is 0.7Bm,the maximum zero-sequence inrush current will be 0.95 IN;the zero-sequence inrush current of multiple transformers is proportional to the number of neutral point grounded transformers. Combined with the setting principle of 220 kV zero-sequence current protection,the influence of zero -sequence inrush current on it is analyzed. The zero-sequence inrush current has no influence on zero-sequence current protection of main transformer and on Zone 1,2 and 4 of line zero-sequence current protection,but has bad influence on Zone 3 of line zero-sequence current protection and bus -link protection. The corresponding measures are put forward for their operation and setting.

关 键 词:变压器 励磁涌流 仿真分析 零序电流保护 

分 类 号:TM773[电气工程—电力系统及自动化]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象