冷冻机蒸发器结垢现象的分析与处理  

Analysis and treatment of fouling phenomenon at refrigerator's evaporator

在线阅读下载全文

作  者:曹景华[1] 姚琳[1] 陈保权[1] 王明莉[1] 

机构地区:[1]安阳钢铁股份有限公司制氧厂,河南省安阳市安钢大道455004

出  处:《深冷技术》2008年第5期19-21,共3页

摘  要:介绍空分设备空气预冷系统低温水泵流量降低,电机温度和膨胀阀开度增加的故障现象,通过对运行参数的对比分析和前期处理,判断故障由冷冻机蒸发器铜管被结晶物堵塞导致换热效果降低引起,对蒸发器进行封闭、循环酸洗,消除了故障。Fault phenomena of the decreased cold water pump's flux in air pre-cooling system, the rising motor temperature and the increased expansion valve opening in an air separation unit are introduced. According to the comparative analysis and pretreatment of the operating parameters, the faults are attributed to the deterioration of heat exchange performance due to the blockage of chiller evaporator's copper tube with crystal substance. The faults were eliminated by closed and circulating pickling of the evaporator.

关 键 词:冷冻机 蒸发器 膨胀阀 结晶物 酸洗 

分 类 号:TB657.8[一般工业技术—制冷工程]

 