检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]华北电力科学研究院有限责任公司,北京市100045
出 处:《电力系统自动化》2008年第19期100-103,共4页Automation of Electric Power Systems
摘 要:通过对某500 kV输电线路断路器取消合闸电阻的投切试验、断路器事故进行分析,并对此进行电磁暂态仿真计算,讨论了500 kV输电线路断路器取消合闸电阻的原则,与线路操作过电压幅值、线路两端高压并联电抗器配置情况的关系。研究结果表明,500 kV输电线路断路器合闸电阻配置时,需要考虑线路高压并联电抗器的配置情况,这将直接影响断路器断开的成功与否。The opening-closing test and circuit breaker fault of circuit breaker without closing resistors in 500 kV transmission lines are analyzed and simulated. The criterion of removing circuit breaker closing resistors is discussed. The relationship between the criterion of removing circuit breaker closing resistors and switching over-voltage magnitude, the HV shunt reactors installed in the two terminals of the line is described. It draws a conclusion that the necessary condition about the criterion of removing circuit breaker closing resistors in 500 kV transmission line should be the scheme of HV shunt reactors of the line.
分 类 号:TM762[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.28