洁净室气密性检测方法研究——国标《洁净室施工及验收规范》编制组研讨系列课题之八  被引量:5

Air tightness measuring method for cleanrooms:part 8 of the series of research practice of the national standard task group for the Code for cleanroom construction and acceptance test

在线阅读下载全文

作  者:曹国庆[1] 许钟麟[1] 张益昭[1] 张彦国[1] 汪亚兵 欧少华 蔡正明 沈晋明[3] 

机构地区:[1]中国建筑科学研究院 [2]上海开纯洁净室技术工程有限公司 [3]同济大学

出  处:《暖通空调》2008年第11期1-6,共6页Heating Ventilating & Air Conditioning

摘  要:分析了在正、负压洁净室进行洁净室气密性验证的重要性,对洁净室气密性相关问题进行了理论计算,给出了具体检测方法,并进行了实验研究。结果表明,一个密封很好的洁净室,500Pa压力的半衰期不足5min,小时泄漏率不到10。Abstract Analyses the importance of air tightness validation of cleanrooms to prevent contamination diffusion. Presents detailed test method and gives some relevant advices for assessing air tightness of cleanrooms on the basis of theoretical calculation and experimental study. The results show that the half-life time of a well tightened cleanroom is less than 5 minutes, and the hourly leak rate is less than 10 percent. Keywords cleanroom, air tightness, pressure decay, half-life time, hourly leak rate

关 键 词:洁净室 气密性 压力衰减 半衰期 小时泄漏率 

分 类 号:TU831.8[建筑科学—供热、供燃气、通风及空调工程]

 