换流变压器套管爆炸事故原因分析  被引量:31

Cause Analysis of an Explosive Accident of Converter Transformer Bushing

在线阅读下载全文

作  者:孙勇[1] 朱建新[2] 

机构地区:[1]中国南方电网超高压输变电公司广州局,广州510405 [2]国网武汉高压研究院,武汉430074

出  处:《南方电网技术》2008年第5期82-83,共2页Southern Power System Technology

摘  要:对一台换流变的套管爆炸事故进行了分析,发现事故是由于套管工艺不良所致,指出该批次套管在电容量变化超过3%时即需更换。结合网内换流变压器油纸电容式套管的运行情况,提出了具体的反事故措施,以便改进和提高换流变压器的运行维护水平。An explosive accident of converter transformer's bushing is analyzed thoroughly. It is found out that the accident is due to inappropriate techniques of the bushing, and it is suggested that if capacitance value of this kind of bushing is above 3% to the factory-tested value, the bushing must be replaced. Combined with operation record of the oil-paper capacitor bushing, the preventive measures are presented to improve operation and maintenance situation of the converter transformer.

关 键 词:套管 换流变压器 局部放电 

分 类 号:TM407[电气工程—电器]

 