500kV变电站35kV并联电容器组常用保护方式及其定值的计算研究  被引量:3

Calculating Research on Common Protection Methods and Rated values of 35 kV Shunt Capacitor Bank in 500 kV Substation

在线阅读下载全文

作  者:赵启承[1] 王敏[2] 丁一岷 

机构地区:[1]浙江省电力试验研究院,杭州310014 [2]浙江省电力公司,杭州310007 [3]浙江嘉兴电力局,浙江嘉兴314033

出  处:《电力电容器与无功补偿》2008年第6期5-9,共5页Power Capacitor & Reactive Power Compensation

摘  要:针对我省500 kV变电站发生的两次35 kV电容器组的带内熔丝电容器爆炸事故所暴露的电容器组保护失效问题,对全省运行中的500 kV变电站35 kV并联电容器组保护定值进行仿真计算研究,分析不同数量内熔丝熔断时的保护信号值和电容器单元及其元件上承受的过电压值,提出相关保护定值的研究意见。According to the capacitor bank protection faults leading to the two explosive accidents of capacitors with internal fuse of 35 kV shunt capacitor bank in 500 kV substations, the computer simulation models of 35 kV shunt capacitor banks in 500 kV substation in Zhejiang Province were conducted. The protection signal values caused by different numbers of internal fuses disconnected and the over-voltage undertaken by the other normal capacitor elements and capacitor units were analyzed through simulation computation, And Related protection values of the relevant capacitor banks were raised.

关 键 词:并联电容器 内熔丝 保护 

分 类 号:TM531.4[电气工程—电器]

 